Yueqing Morele Import & Export Co.,Ltd

CJX2N series ac contactor

CJX2N series ac contactor

Product introduction:


Product Keywords:
CJX2N AC Contactor

Call Us:
0086-577-62780991 

Online Service:

 leo@chmorele.com              PDF Download
 leo.luo1986                            008618657725669
 leoluo1986                              2201537327


  • Product description

    CJX2N series AC contactor is suitable for frequency 50/60Hz,rated insulation voltage up to 1000V,rated operation current 9~150A under AC-3 duty.It is mainly used for making/breaking electric circuits at a long distance & for frequent starting/stopping & controlling AC Motors.It is used in combination with thermal relay to compose a magnetic motor starter.
    The products com-ply with IEC60947-4-1 standard.

    Main Technical Parameter

    Type CJX2N-09 CJX2N-12 CJX2N-18 CJX2N-25 CJX2N-32 CJX2N-38 CJX2N-40
    Rated working current Ie (A)
    AC-3 Ue≤440V
    9 12 18 25 32 38 40
    Rated hear current Ith (A) 25 25 32 40 50 50 60
    Rated insulation voltage Ui (V) 690 690 690 690 690 690 1000
    Rated operating voltage Ue (V) Max 690 690 690 690 690 690 1000
    Rated operational power in AC-3 Pe (KW) 220/230V 2.2 3 4 5.5 7.5 9 11
    380/400V 4 5.5 7.5 11 15 18.5 18.5
    415/440V 4 5.5 9 11 15 18.5 22
    500V 5.5 7.5 10 15 18.5 18.5 22
    660/690V 5.5 7.5 10 15 18.5 18.5 30
    Rated operational power inAC-4 Pe (KW) 220/230V 1.5 1.5 2.2 3 4 4 4
    380/400V 2.2 3.7 4 5.5 7.5 7.5 9
    415/440V 2.2 3 3.7 5.5 7.5 7.5 9/11
    500V 3 4 5.5 7.5 9 9 11
    660/690V 4 5.5 7.5 10 11 11 15
    Frequency of operation (I/h)   1200 1200 1200 1200 1000 1000 1000
    Electrical endurance (x104) AC-3 100 100 100 100 80 80 80
    AC-4 20 20 20 20 20 20 15
    Mechanical endurance (x106)   15 15 15 15 15 15 6
    Operating voltage range of coil Close voltage:(0.85~1.1)Us Open voltage:(20%~75%)Us
    Power consumption of coil (VA) Atracting 7 7 7 7 7 7 20
    Starting 70 70 70 70 70 70 200
    Rated insulation voltage ofauxitiary contacts (V) 690 690 690 690 690 690 690 690
    Conventional thermal current ofauxitiary contacts (A) 10 10 10 10 10 10 10 10
    Auxitiary contacts speecification AC-15:360VA DC-13:33W

    Type CJX2N-50 CJX2N-65 CJX2N-80 CJX2N-95 CJX2N-115 CJX2N-150
    Rated working current Ie (A)
    AC-3 Ue≤440V
    50 65 80 95 115 150
    Rated hear current Ith (A) 80 80 125 125 200 200
    Rated insulation voltage Ui (V) 1000 1000 1000 1000 1000 1000
    Rated operating voltage Ue (V) Max 1000 1000 1000 1000 1000 1000
    Rated operational power in AC-3 Pe (KW) 220/230V 15 18.5 22 25 30 40
    380/400V 22 30 37 45 55 75
    415/440V 25/30 37 45 45 59 80
    500V 30 37 55 55 75 90
    660/690V 33 37 45 45 80 100
    Rated operational power inAC-4 Pe (KW) 220/230V 5.5 7.5 7.5 9 9 11
    380/400V 11 11 15 15 18.5 22
    415/440V 11 11/15 15 15 18.5 22
    500V 15 18.5 22 22 30 37
    660/690V 18.5 22 25 25 30 45
    Frequency of operation (I/h)   1000 1000 750 750 750 750
    Electrical endurance (x104) AC-3 60 60 60 60 60 60
    AC-4 15 15 15 15 15 15
    Mechanical endurance (x106)   6 6 4 4 4 4
    Operating voltage range of coil Close voltage:(0.85~1.1)Us Open voltage:(20%~75%)Us
    Power consumption of coil (VA) Atracting 20 20 20 20 22 22
    Starting 200 200 200 200 300 300
    Rated insulation voltage ofauxitiary contacts (V) 690 690 690 690 690 690 690
    Conventional thermal current ofauxitiary contacts (A) 10 10 10 10 10 10 10
    Auxitiary contacts speecification AC-15:360VA DC-13:33W

        Standard Control Circuit Voltage
    Volts 24 42 48 110 220 230 240 380 400 415 440 500 600
    50Hz B5 D5 E5 F5 M5 P5 U5 Q5 V5 N5 R5 S5 Y5
    60Hz B6 D6 E6 F6 M6 - U6 Q6 - - R6 - -
    50/60Hz B7 D7 E7 F7 M7 P7 U7 Q7 V7 N7 R7 - -

    Outline & Dimensions

  •   
  • Relative Products: